P.T Potential transformer
We know that measuring high voltage in transmission and
distribution systems is not very easy. Instrument transformers P.T (potential
transformers) are used to measure high voltage.
Details about Instrument Transformer
Current transformers are used to measure the current in the
transmission and distribution lines, and potential or voltage transformers are
used to measure the voltage.
Read more about current transformers C.T
“Potential transformers are also called voltage
transformers. It is a transformer that converts a large amount of voltage to a
low range. It is used to measure high voltage in a circuit with a low range
meter. "
We know that in order to measure voltage, the meter has to
be connected in parallel with the load. The basic principle and function of a
potential transformer are very similar to that of a standard power transformer.
Potential transformers are called short P.T.
Function and operation of the potential transformer.
From the figure above, the primary side is basically the
high voltage side and the secondary side is the low voltage side. The number of
punches in the primary winding of a potential transformer is higher than that
of the secondary winding. So this is a step-down transformer. There is a
voltmeter attached to the secondary winding with which I can measure the
voltage.
The secondary voltage of PT is usually designed to be 110
volts. Since the potential coils of PT voltmeters and other meters have high
impedance, there will be a small current flow in PT secondary. This is why PT
behaves like a two-winding transformer in no-load conditions. PT has a very low
VA rating due to its low load. The secondary side is grounded with one edge for
safety convenience.
PT transformation ratio like normal transformer.
V1 / V2 = N1 / N2
The high voltage side can be measured if the readings of the
voltmeter and the transformation ratio are known from the above equations.
However, this is true in the case of the ideal voltage
transformer. But not entirely correct in the case of the actual PT. This is
because the voltage drops in the primary and secondary windings of the PT. This
is usually due to the power factor, resistance. Therefore, the ratio of PT and
phase angle error can be seen.
Potential Transformer Error:
Is - Secondary current.
Es - Secondary induced emf.
Vs - Secondary terminal voltage.
Rs - Secondary winding resistance.
Xs - Secondary winding reactance.
Ip - Primary current.
Ep - Primary induced emf.
Vp - Primary terminal voltage.
Rp - Primary winding resistance.
Xp - Primary winding reactance.
KT - Turns ratio = Numbers of primary turns/number of
secondary turns.
I0 - Excitation current.
Im - Magnetizing component of I0.
Iw - Core loss component of I0.
Φm - Main flux.
β - Phase angle error.
In the case of a current transformer, the primary current Ip
is the vector sum of the excitation current and this current is equal to the
inverse of the secondary current which is also a 1 / Kt ratio.
Then, Ip = (Io + Is) / Kt
If Vp system voltage is supplied to the primary of the PT
then the voltage will drop due to resistance in the primary winding where the
primary current Ip will also come. Ep can be found after this voltage drop Vp
is omitted. This Ep is equal to the primary induced E, M, F.
This primary E, M, F will be converted to secondary winding
by mutual induction. Again this Es voltage will drop due to the presence of
resistance and reactance in the secondary winding. As a result, it can be found
in the Burden terminal which is expressed by Vs.
If you do not know Burden, note the text below
Ideally, if the system voltage is Vp, then the secondary
voltage of the PT will be: Vp / Kt, but in reality, the actual secondary voltage
of the PT is Vs.
So the difference between the ideal value Vp / Kt and the
actual value Vs is voltage error or ratio error. It is expressed by the
following equation:
Application of Potential Transformer:
- In electric metering system
- In the electric protection system
- In the synchronizing generator with the grid.
- In the impedance protection of the generator.
PT Burden:
Burden basically refers to the operant power
which is related to the potential transformer. The Burden rating of the
transformer provides the highest value of the operating power that the
transformer typically performs under certain conditions. The actual burden is
the value of the actual operant power with the output load of the transformer.
0 মন্তব্যসমূহ